FishtapeCalculations for electricians

Wire sizing step by step, on one circuit →

A free calculator from the Fishtape app. Same engine as the app. The app adds current capacity with derating, your code and edition, saved jobs and offline use.
See the app →

Wire gauge chart

AWG and kcmil sizes with diameter, area in mm², circular mils and resistance. Every figure on this page is calculated from the gauge formula, not copied from a table.

AREA
—
DIAMETER
—
CIRCULAR MILS
—
RESISTANCE
—
PER 1000 FT
—
NEAREST METRIC SIZE, FOR ORIENTATION ONLY
—
The calculation sheet

Where these numbers come from

AWG is a geometric series with two fixed points. 36 AWG is 0.005 inch across, and 0000 AWG, written 4/0, is 0.46 inch. Between them are 39 steps, each the same ratio apart:

d = 0.005 × 92(36 − n) / 39 inch

Here n is the gauge number, with n = 0, −1, −2, −3 for 1/0 to 4/0. The area is π/4 × d². A circular mil is the area of a circle one thousandth of an inch across, so the circular mils are the diameter in mils, squared.

That’s why the whole table below can be calculated, and none of it comes from anyone’s copyrighted table. Sizes above 4/0 aren’t part of the gauge series. They’re named by area in thousands of circular mils, which is what kcmil means.

Why bigger numbers mean thinner wire

The gauge number roughly counts how many times the wire was drawn through a smaller die. More passes, thinner wire: 24 AWG is thin, 2 AWG isn’t. The numbers run out below one pass, so the big sizes are written 1/0, 2/0, 3/0 and 4/0.

Two rules of thumb come from the ratio: every 3 gauge numbers doubles or halves the area, and every 10 changes it about tenfold.

AWG and mm² don’t mix

The nearest metric column is only a rough guide. 4 AWG is 21.15 mm². That’s close to 25 mm² but not the same, and you can’t order 25 mm² from a North American supplier anyway. Swapping one for the other without noticing is how errors get into a design, so this site keeps the two apart. The nearest size in the other system is shown only as a note, with the difference in per cent.

The resistance columns

The resistance in the table is for a solid conductor at 20 °C, worked out as ρ/A from the resistivity of the metal: 1.7241 × 10−8 Ω·m for annealed copper at 100 % IACS, 2.8264 × 10−8 for aluminium at 61 %. In practice two things change it, and the calculator above handles both:

  • Stranding. The strands spiral, so they’re longer than the cable. The usual allowance is about 2 %, so the calculator uses 1.02 by default.
  • Temperature. Copper resistance goes up about 0.39 % per degree. At 75 °C it’s about 22 % higher than at 20 °C, which is why a voltage drop worked out at room temperature comes out too low.

If you need the drop along a run, use the voltage drop calculator.

AWG and kcmil

Diameter, area, circular mils and the resistance of a solid conductor at 20 °C, calculated from the formula above.

SizeDiameter
mm
Diameter
in
Area
mm²
Circular
mils
Copper
Ω/km
Copper
Ω/1000 ft
Aluminium
Ω/km
Nearest
metric
36 AWG0.1270.0050.01267251361414.822310.5 mm² -97%
35 AWG0.14260.0056150.0159732107932917690.5 mm² -97%
34 AWG0.16010.0063050.0201440856260.914030.5 mm² -96%
33 AWG0.17980.007080.025450678.8206.911130.5 mm² -95%
32 AWG0.20190.007950.0320363538.3164.1882.50.5 mm² -94%
31 AWG0.22680.0089280.0403980426.9130.1699.80.5 mm² -92%
30 AWG0.25460.010030.05093101338.5103.25550.5 mm² -90%
29 AWG0.28590.011260.06422127268.581.83440.10.5 mm² -87%
28 AWG0.32110.012640.08098160212.964.93490.5 mm² -84%
27 AWG0.36060.01420.1021202168.951.47276.80.5 mm² -80%
26 AWG0.40490.015940.1288254133.940.81219.50.5 mm² -74%
25 AWG0.45470.01790.1624320106.232.37174.10.5 mm² -68%
24 AWG0.51060.02010.204740484.2125.67138.10.5 mm² -59%
23 AWG0.57330.022570.258250966.7820.36109.50.5 mm² -48%
22 AWG0.64380.025350.325564252.9616.1486.820.5 mm² -35%
21 AWG0.72290.028460.41058104212.868.850.5 mm² -18%
20 AWG0.81180.031960.51761,02233.3110.1554.60.5 mm² +4%
19 AWG0.91160.035890.65271,28826.418.05143.30.75 mm² -13%
18 AWG1.0240.04030.8231,62420.956.38534.340.75 mm² +10%
17 AWG1.150.045261.0382,04816.615.06327.231 mm² +4%
16 AWG1.2910.050821.3092,58313.174.01521.61.5 mm² -13%
15 AWG1.450.057071.653,25710.453.18417.131.5 mm² +10%
14 AWG1.6280.064082.0814,1078.2852.52513.582.5 mm² -17%
13 AWG1.8280.071962.6245,1786.5712.00310.772.5 mm² +5%
12 AWG2.0530.080813.3096,5305.2111.5888.5424 mm² -17%
11 AWG2.3050.090744.1728,2344.1321.266.7744 mm² +4%
10 AWG2.5880.10195.26110,3833.2770.99885.3726 mm² -12%
9 AWG2.9060.11446.63413,0932.5990.79214.266 mm² +11%
8 AWG3.2640.12858.36616,5102.0610.62823.37910 mm² -16%
7 AWG3.6650.144310.5520,8181.6340.49822.67910 mm² +5%
6 AWG4.1150.16213.326,2511.2960.39512.12516 mm² -17%
5 AWG4.6210.181916.7733,1021.0280.31331.68516 mm² +5%
4 AWG5.1890.204321.1541,7410.81520.24851.33625 mm² -15%
3 AWG5.8270.229426.6752,6350.64640.1971.0625 mm² +7%
2 AWG6.5440.257633.6366,3710.51270.15630.840435 mm² -4%
1 AWG7.3480.289342.4183,6930.40660.12390.666535 mm² +21%
1/0 AWG8.2510.324953.48105,5350.32240.098270.528550 mm² +7%
2/0 AWG9.2660.364867.43133,0770.25570.077930.419270 mm² -4%
3/0 AWG10.40.409685.03167,8060.20280.06180.332495 mm² -10%
4/0 AWG11.680.46107.2211,6000.16080.049010.263695 mm² +13%
250 kcmil12.70.5126.7250,0000.13610.041480.2231120 mm² +6%
300 kcmil13.910.5477152300,0000.11340.034570.1859150 mm² +1%
350 kcmil15.030.5916177.3350,0000.097220.029630.1594185 mm² -4%
400 kcmil16.060.6325202.7400,0000.085060.025930.1394185 mm² +10%
500 kcmil17.960.7071253.4500,0000.068050.020740.1116240 mm² +6%
600 kcmil19.670.7746304600,0000.056710.017280.09297300 mm² +1%
700 kcmil21.250.8367354.7700,0000.048610.014820.07969400 mm² -11%
750 kcmil220.866380750,0000.045370.013830.07437400 mm² -5%
800 kcmil22.720.8944405.4800,0000.042530.012960.06972400 mm² +1%
900 kcmil24.10.9487456900,0000.037810.011520.06198500 mm² -9%
1000 kcmil25.41506.71,000,0000.034030.010370.05578500 mm² +1%
1250 kcmil28.41.118633.41,250,0000.027220.0082970.04462630 mm² +1%
1500 kcmil31.111.225760.11,500,0000.022680.0069140.03719800 mm² -5%
1750 kcmil33.61.323886.71,750,0000.019440.0059260.03187800 mm² +11%
2000 kcmil35.921.41410132,000,0000.017010.0051850.027891000 mm² +1%

Resistance is for a solid conductor at 20 °C, from ρ/A. Stranded conductors are about 2 % higher, and copper gains about 0.39 % per degree. The last column is a rough guide only: the two systems aren’t interchangeable.

Metric conductor sizes

The IEC 60228 sizes used outside North America, with the same columns. Metric sizes are defined by area, so the diameter shown is for a solid round conductor of that area.

SizeDiameter
mm
Diameter
in
Area
mm²
Circular
mils
Copper
Ω/km
Copper
Ω/1000 ft
Aluminium
Ω/km
Nearest
AWG or kcmil
0.5 mm20.79790.031410.598734.4810.5156.5320 AWG -3%
0.75 mm20.97720.038470.751,48022.997.00737.6918 AWG -9%
1 mm21.1280.0444211,97417.245.25528.2617 AWG -4%
1.5 mm21.3820.054411.52,96011.493.50318.8415 AWG -9%
2.5 mm21.7840.070242.54,9346.8962.10211.3113 AWG -5%
4 mm22.2570.0888547,8944.311.3147.06611 AWG -4%
6 mm22.7640.1088611,8412.8730.87584.7119 AWG -10%
10 mm23.5680.14051019,7351.7240.52552.8267 AWG -5%
16 mm24.5140.17771631,5761.0780.32841.7665 AWG -5%
25 mm25.6420.22212549,3380.68960.21021.1313 AWG -6%
35 mm26.6760.26283569,0730.49260.15010.80752 AWG +4%
50 mm27.9790.31415098,6760.34480.10510.56531/0 AWG -6%
70 mm29.4410.371770138,1470.24630.075070.40382/0 AWG +4%
95 mm2110.43395187,4850.18150.055320.29753/0 AWG +12%
120 mm212.360.4866120236,8230.14370.043790.2355250 kcmil -5%
150 mm213.820.5441150296,0290.11490.035030.1884300 kcmil -1%
185 mm215.350.6042185365,1020.093190.028410.1528350 kcmil +4%
240 mm217.480.6882240473,6460.071840.02190.1178500 kcmil -5%
300 mm219.540.7695300592,0580.057470.017520.09421600 kcmil -1%
400 mm222.570.8885400789,4100.04310.013140.07066800 kcmil -1%
500 mm225.230.9934500986,7630.034480.010510.056531000 kcmil -1%
630 mm228.321.1156301,243,3210.027370.0083410.044861250 kcmil -1%
800 mm231.921.2578001,578,8200.021550.0065690.035331500 kcmil +5%
1000 mm235.681.40510001,973,5250.017240.0052550.028262000 kcmil -1%

Resistance is for a solid conductor at 20 °C, from ρ/A. Stranded conductors are about 2 % higher, and copper gains about 0.39 % per degree. The last column is a rough guide only: the two systems aren’t interchangeable.

What a size chart can’t tell you

How much current a wire can carry. That depends on the insulation, the ambient temperature, how many loaded conductors are bundled together, how it’s installed, and the rules where you work. Those figures are in national wiring rules, which are copyrighted, so they aren’t here.

The app works through all of it at once and tells you which check decided the size. See the app.

More free calculators

The app

Fishtape does the rest

Current capacity with derating, for your code and edition. Short circuit, protective conductor, transformer fault current and conduit fill. Sheets saved by job, and all of it works offline. Leave your email and we’ll send the link.

€1.99 a month, or €29.99 once, for everything. Free for 7 days.

Cable size screen: one size that passes every check, with the binding constraint named